Find a course

Module 5: Heat Engines, Refrigerators and Real CyclesLesson 10 of 1115 min

Refrigerators and Heat Pumps

How refrigerators and heat pumps use work to move heat from cold to hot, how to calculate COP, and why heat pumps beat electric resistance heat.

Step 1 of 12Learn

More heat than you pay for

An electric space heater turns 1 kilowatt-hour of electricity into exactly 1 kilowatt-hour of heat. That's the best a resistance heater can do.

A heat pump using the same 1 kWh can deliver 3 or 4 kWh of heat into a home on a mild winter day. That sounds like it breaks the first law, but it doesn't. A heat pump doesn't make heat from electricity; it uses the electricity to move heat that already exists in the outdoor air or ground into the house. Even air at 0 °C contains plenty of internal energy; it's 273 kelvins above absolute zero.

Refrigerators, freezers and air conditioners are the same kind of machine, just used for cooling instead of heating. They pump heat out of a cold space and dump it into a warmer one. Put your hand behind or under a refrigerator and you'll feel the heat it's removing from the food, plus the energy from its compressor.

These machines are heat engines run in reverse. Instead of letting heat flow from hot to cold and extracting work, they take in work to drive heat from cold to hot, exactly what the Clausius statement says can't happen on its own.

Step 2 of 12Learn

Coefficient of performance

A refrigerator or heat pump takes in work W, extracts heat Qc from the cold space, and delivers heat Qh to the hot space. Energy conservation gives:

Qh = Qc + W

Instead of efficiency, these devices are rated by a coefficient of performance (COP), the useful heat moved per unit of work:

  • Refrigerator or air conditioner (we want cooling): COP(cooling) = Qc / W
  • Heat pump (we want heating): COP(heating) = Qh / W

Since Qh = Qc + W, COP(heating) = COP(cooling) + 1 for the same machine.

Unlike efficiency, COP is usually greater than 1. A kitchen refrigerator typically has a COP of around 2–3; a modern air-source heat pump on a mild day, around 3–4.

The second law sets a maximum, again found from a reversible Carnot cycle run backward:

COP(cooling, max) = Tc / (Th − Tc)

COP(heating, max) = Th / (Th − Tc)

The smaller the temperature gap, the higher the possible COP. That's why heat pumps work best in mild weather and lose performance as the outdoor temperature drops, and why ground-source heat pumps, which draw from soil that stays around 10 °C year-round, usually beat air-source ones in cold climates.

Step 3 of 12Practice · Work it out

A heat pump delivers 12 kJ of heat into a house while using 3 kJ of electrical work. What is its heating COP?

Step 4 of 12Try the calculator

Heat pump and refrigerator limits

Ideal (Carnot) coefficients of performance for given indoor and outdoor temperatures. Real devices achieve roughly 40–60% of these values.

Maximum heating COP
14
Maximum cooling COP
13
Realistic heating COP (50% of ideal)
7

Step 5 of 12Chart

Heat pump COP falls as it gets colder outside

Indoor temperature 20 °C. The bigger the temperature lift, the harder the pump works for each unit of heat it delivers.

Heat pump COP falls as it gets colder outsideLine chart with 4 categories: 10 °C: Carnot limit 29.3, Typical real unit 4.5; 0 °C: Carnot limit 14.7, Typical real unit 3.5; −10 °C: Carnot limit 9.8, Typical real unit 2.7; −20 °C: Carnot limit 7.3, Typical real unit 2.1.0102030Heating COP10 °C0 °C−10 °C−20 °COutdoor temperature
The real-unit line is illustrative; actual models vary widely.
Heat pump COP falls as it gets colder outside
Outdoor temperatureCarnot limitTypical real unit
10 °C29.34.5
0 °C14.73.5
−10 °C9.82.7
−20 °C7.32.1

Step 6 of 12Learn

The vapor-compression cycle

Most refrigerators, air conditioners and heat pumps use the vapor-compression cycle. A working fluid, the refrigerant, circulates through a closed loop and changes between liquid and gas, using latent heat to move large amounts of energy:

  1. Evaporator (inside the cold space): the refrigerant enters as a cold, low-pressure liquid. It absorbs heat from the food or room and boils into vapor, even though it's cold, because its boiling point is very low at that pressure.
  2. Compressor: an electric motor compresses the vapor. Its pressure and temperature rise sharply, nearly adiabatically, until it's hotter than the surroundings outside.
  3. Condenser (the coils behind or under a refrigerator, or the outdoor unit of an air conditioner): the hot vapor releases heat to the warmer surroundings and condenses into a liquid.
  4. Expansion valve: the high-pressure liquid passes through a narrow opening, its pressure drops suddenly, and some of it flashes to vapor, cooling the mixture sharply. The cold liquid returns to the evaporator.

A heat pump uses the same loop, with the evaporator outdoors and the condenser indoors. Many units have a reversing valve that swaps the roles, so one machine heats in winter and cools in summer.

Older refrigerants such as CFCs damaged the ozone layer and were phased out under the 1987 Montreal Protocol. Their replacements are being phased down too, because many are potent greenhouse gases.

Step 7 of 12Practice · Put in order

Put the stages of the vapor-compression cycle in order, starting as cold refrigerant enters the evaporator.

Drag the items, or use the arrow buttons, to put them in order.

  1. The expansion valve drops the pressure and cools the liquid
  2. The compressor raises the vapor's pressure and temperature
  3. Refrigerant absorbs heat and boils in the evaporator
  4. Hot vapor releases heat and condenses in the condenser

Step 8 of 12Diagram

The vapor-compression loop

The vapor-compression loopCycle diagram: Evaporator → Compressor → Condenser → Expansion valve.RefrigerantEvaporatorCompressorCondenserExpansion valve

Tap a shape with to see more.

Evaporator

Cold, low-pressure refrigerant boils and absorbs heat from the space being cooled.

Compressor

Uses electrical work to squeeze the vapor, making it hotter than the outdoors.

Condenser

Hot vapor releases heat to the room or outdoors and condenses to liquid.

Expansion valve

Pressure drops suddenly, and the liquid cools far below the cold-space temperature.

Step 9 of 12Practice · Work it out

What is the maximum (Carnot) cooling COP of a freezer that keeps its interior at 253 K in a kitchen at 298 K? Round to one decimal place.

Step 10 of 12Tap to reveal

Reading heat pump and air conditioner ratings

  1. COP

    The ratio of heat moved to electrical energy used, measured at one specific set of temperatures. A COP of 3 means 3 kWh of heat for each kWh of electricity.

  2. Seasonal ratings

    Because COP changes with outdoor temperature, many countries rate units over a typical season. In the US, cooling uses SEER (BTU of cooling per watt-hour) and heating uses HSPF. Higher numbers mean lower running costs.

  3. Capacity

    How much heat a unit can move per hour, in kilowatts or in BTU per hour. In the US, air conditioners are often sized in "tons": 1 ton is 12,000 BTU per hour, about 3.5 kW, originally the cooling from melting a ton of ice in a day.

  4. Cold-climate performance

    Check both the COP and the heating capacity at low outdoor temperatures such as −15 °C. As the temperature gap grows, both fall, so some systems need backup heat on the coldest days.

Step 11 of 12Practice · True or false

A heat pump with a heating COP of 3.5 violates the first law of thermodynamics, because it delivers more energy than it consumes.

Step 12 of 12Practice · What would you do?

What would you do?

A family wants to cut their heating bill in a region where winters are mild, usually around 2–8 °C. They are choosing between an electric resistance heater and an air-source heat pump, both using electricity at the same price. Which choice uses less electricity for the same heat, and why?