Module 3: Heating, Cooling and Hot WaterLesson 5 of 1015 min

Heating and Cooling Systems

Read AFUE, SEER2 and HSPF2 ratings, see why heat pumps deliver more heat than the energy they use, and save with thermostat settings and sealed ducts.

Step 1 of 14Learn

A machine that moves heat

In winter, a gas furnace burns fuel and turns most of its energy into heat for your home. A modern condensing furnace can reach about 95–98% efficiency. That sounds hard to beat. Yet a heat pump routinely delivers 250–400%: for every unit of electricity it uses, it provides two and a half to four units of heat. How is that possible without breaking the laws of physics?

A heat pump does not create heat; it moves it. It works like a refrigerator running in reverse. A refrigerant absorbs heat from the outdoor air, even cold winter air, because the refrigerant is colder still. A compressor squeezes the refrigerant, raising its temperature, and an indoor coil releases that heat into the house. In summer the process reverses and the same machine works as an air conditioner, pumping heat out of the house.

The ratio of heat delivered to electricity used is the coefficient of performance (COP). A COP of 3 means 3 kWh of heat for 1 kWh of electricity. COP falls as the outdoor temperature drops, because there is less heat to gather, but modern cold-climate heat pumps keep working efficiently well below freezing, many still delivering heat with a COP around 1.5–2 at −15 °C (5 °F) or lower.

Types include ducted air-source heat pumps (replacing a furnace and central air), ductless mini-splits (individual indoor heads, ideal for homes without ducts or for additions), and ground-source (geothermal) heat pumps, which exchange heat with the ground through buried pipes for very high efficiency but at a higher installation cost.

Step 2 of 14Practice · Choose one

How can a heat pump deliver three units of heat for every unit of electricity it uses?

Step 3 of 14Diagram

How a heat pump heats a house

The refrigerant runs a loop: it picks up heat outdoors, gets squeezed to a higher temperature, and gives that heat up indoors. In summer the loop simply runs the other way.

How a heat pump heats a houseCycle diagram: Outdoor coil absorbs heat → Compressor squeezes it → Indoor coil releases heat → Expansion valve.Heat moved,not madeOutdoor coilabsorbs heatCompressorsqueezes itIndoor coilreleases heatExpansion valve

Tap a shape with to see more.

Outdoor coil absorbs heat

Very cold refrigerant picks up heat even from 20 °F air.

Compressor squeezes it

Compressing the gas raises its temperature well above room temperature. This is where the electricity goes.

Indoor coil releases heat

A fan blows house air over the hot coil.

Expansion valve

Pressure drops, the refrigerant gets very cold again and the loop restarts.

Step 4 of 14Learn

Efficiency ratings decoded

Heating and cooling equipment comes with efficiency ratings. In the US:

  • AFUE (Annual Fuel Utilization Efficiency) for furnaces and boilers: the percentage of fuel energy that becomes heat over a typical year. Older furnaces may be 60–70%; standard non-condensing models about 80%; condensing models 90–98%, because they capture extra heat from water vapor in the exhaust.
  • SEER2 (Seasonal Energy Efficiency Ratio) for air conditioners and heat pumps in cooling mode: cooling output in BTU divided by electricity in watt-hours over a typical season. Higher is better. Federal minimums since 2023 are about 13.4–14.3 SEER2 depending on region, while high-efficiency units exceed 20.
  • HSPF2 (Heating Seasonal Performance Factor) for heat pumps in heating mode: heating output in BTU per watt-hour over a season. Higher is better; dividing HSPF2 by 3.412 gives a rough seasonal COP.
  • ENERGY STAR labels mark models that beat minimum standards by a meaningful margin, and ENERGY STAR Most Efficient marks the top performers.

Ratings let you compare running costs. Cooling cost scales inversely with SEER2: replacing a 10 SEER unit with a 16 SEER2 unit (roughly comparable scales) cuts cooling electricity by about 1 − 10/16 ≈ 37%.

Sizing matters as much as efficiency. Oversized equipment, very common in practice, short-cycles: it turns on and off frequently, wastes energy, wears out faster and, for air conditioners, removes less humidity, leaving rooms clammy. Contractors should perform a Manual J load calculation (or equivalent) based on your home's actual insulation, windows and air tightness, not simply match the size of the old unit. After air sealing and insulation, the right size is often smaller.

Step 5 of 14Note

Step 6 of 14Practice · Match the pairs

Match each rating to the equipment and mode it describes.

Tap an answer, then tap the place where it belongs (or drag it there).

  1. AFUE
  2. SEER2
  3. HSPF2
  4. COP

Step 7 of 14Practice · Work it out

An old furnace is 70% efficient (AFUE) and the home needs 600 therms of delivered heat per year. How many therms of gas does the furnace burn per year? Round to the nearest whole therm.

Step 8 of 14Try the calculator

Furnace vs heat pump running cost

Compare the yearly cost of delivering the same heat with a gas furnace and with a heat pump.

Gas furnace cost per year
754 $
Heat pump cost per year
857 $
Heat pump electricity used
5,357 kWh

Step 9 of 14Note

Step 10 of 14Learn

Thermostats and ducts

Two often-overlooked parts of the system can save a lot: the controls and the ducts.

Thermostat settings. The US Department of Energy estimates you can save as much as 10% a year on heating and cooling by turning your thermostat back 7–10 °F (about 4–6 °C) for 8 hours a day, such as while you sleep or are at work. The less the house is heated, the more slowly it loses heat, so setbacks save energy; the idea that reheating uses more energy than you saved is a myth for furnaces and boilers.

Practical targets many people find comfortable: around 68 °F (20 °C) when awake in winter and lower when asleep or away; 78 °F (26 °C) in summer when home, higher when away.

Programmable and smart thermostats automate schedules. Smart models learn routines, detect when nobody is home and can join utility demand response programs. They only save energy if they are set up properly, though.

One caution for heat pumps: deep setbacks can trigger inefficient backup electric resistance heat when the system recovers. Use modest setbacks or a thermostat designed for heat pumps.

Ducts. In homes with forced-air systems, ENERGY STAR estimates typical duct systems lose 20–30% of the air they move through leaks, holes and poorly connected joints. Ducts running through attics, crawl spaces or garages waste even more by losing heat through their walls. Sealing joints with mastic or foil tape (not ordinary cloth "duct tape," which fails over time) and insulating ducts in unconditioned spaces can make rooms more comfortable and cut heating and cooling bills noticeably.

Step 11 of 14Practice · Sort into groups

Sort these statements about heating and cooling into facts and myths.

Tap an item, then tap its group (or drag it there).

Step 12 of 14Practice · True or false

Modern cold-climate heat pumps can keep heating homes efficiently at temperatures well below freezing.

Step 13 of 14Practice · Chart

Heat delivered per unit of energy used

A furnace can never deliver more heat than the fuel contains. A heat pump moves heat, so it delivers more than it consumes even in cold weather.

Which option delivers the most heat per unit of energy?

Tap the bar that answers the question, then press Check.

Heat delivered per unit of energy usedBar chart with 5 categories: Old furnace (70% AFUE): 0.7; Condensing furnace (96%): 0.96; Electric baseboard: 1; Heat pump at 5 °F: 2; Heat pump at 47 °F: 3.5.01234Old furnace (70% AFUE)0.7Condensing furnace (96%)0.96Electric baseboard1Heat pump at 5 °F2Heat pump at 47 °F3.5
Typical values; heat pump COP varies by model and outdoor temperature.
Heat delivered per unit of energy used
ItemUnits of heat per unit of energy
Old furnace (70% AFUE)0.7
Condensing furnace (96%)0.96
Electric baseboard1
Heat pump at 5 °F2
Heat pump at 47 °F3.5

Step 14 of 14Practice · What would you do?

What would you do?

A family's 22-year-old gas furnace and 18-year-old air conditioner both need replacing. Their home was air sealed and insulated last year. Which approach makes the most sense?