Module 2: How the Grid WorksLesson 4 of 1016 min

Balancing Supply and Demand Every Second

Learn why grid frequency must stay near 60 or 50 hertz, how daily load curves shape the grid, and how operators use reserves to stay balanced.

Step 1 of 15Learn

A grid has almost no storage

Most products sit in warehouses before they are sold. Electricity, until recently, could not. The grid itself stores almost no energy, so supply must equal demand at every instant. If a large power plant suddenly trips offline, the gap must be filled within seconds, or the grid starts to fail.

How do operators know whether supply and demand are balanced? They watch the frequency: how many times per second AC current reverses direction. North America runs at 60 hertz (Hz); Europe, most of Asia, Africa and Australia run at 50 Hz.

Frequency is tied to how fast all the big generators spin. When demand exceeds supply, the extra load acts like a brake on every generator, they slow down slightly, and frequency drops. When supply exceeds demand, generators speed up and frequency rises. Think of a cyclist on a hill: pedal force is supply, the hill is demand, and speed is frequency.

Operators keep frequency within a narrow band, usually within a few hundredths of a hertz of the target. If frequency falls too far, around 59.3 Hz in parts of North America, automatic systems begin underfrequency load shedding: they cut power to blocks of customers on purpose to save the rest of the grid. Generators also trip off to protect themselves if frequency strays too far, which can turn a small imbalance into a cascade. In February 2021, Texas came within minutes of a total collapse that could have taken weeks to restart.

Step 2 of 15Practice · Choose one

A large power plant in a 60 Hz grid suddenly shuts down. What happens to the grid frequency in the first moments?

Step 3 of 15Note

Step 4 of 15Diagram

Frequency danger zones in ERCOT (Texas)

Small deviations from 60 Hz are routine. Larger drops trigger automatic, increasingly drastic responses.

Frequency danger zones in ERCOT (Texas)Scale: Normal: 60.00 Hz, Feb 15, 2021 low, Load shedding stage 1, Load shedding stage 2, Load shedding stage 3.RoutineEmergency5858.55959.56060.558.5 HzLoad shedding stage358.9 HzLoad shedding stage259.3 HzLoad shedding stage159.4 HzFeb 15, 2021 low60 HzNormal: 60.00 Hz

Tap a shape with to see more.

Thresholds simplified from ERCOT's under-frequency load shedding scheme.
Normal: 60.00 Hz

Frequency normally stays within a few hundredths of a hertz of 60.

Feb 15, 2021 low

Frequency stayed below 59.4 Hz for over four minutes; nine minutes would have tripped generators.

Load shedding stage 1

Relays automatically disconnect a first block of customers.

Load shedding stage 2

A second block of load is dropped.

Load shedding stage 3

A third block. Below this, generators begin protecting themselves and a total blackout becomes likely.

Step 5 of 15Learn

Inertia and the first seconds

In the first few seconds after a plant trips, nothing has time to react except physics. The massive spinning rotors of thousands of turbines and generators store kinetic energy, called inertia. As they slow slightly, they release that energy into the grid, buying precious time. More inertia means frequency falls more slowly.

The response then comes in layers:

  1. Inertia (instant): stored rotational energy slows the frequency drop.
  2. Primary frequency response (seconds): generator controls called governors automatically open valves or adjust output when they sense frequency falling. Batteries can respond even faster, in milliseconds.
  3. Secondary response (minutes): the grid operator's central control system, called automatic generation control, signals selected plants to raise output and restore frequency to the target.
  4. Tertiary reserves (tens of minutes): operators bring additional plants online to replace the reserves that were used, so the grid is ready for the next event.

Solar panels, batteries and most wind turbines connect through power-electronic inverters, not spinning generators directly, so they provide no natural inertia. As they replace coal and gas plants, grids have less inertia. Engineers are responding with grid-forming inverters that mimic inertia in software, fast battery response, and synchronous condensers, which are generators that spin without fuel purely to stabilize the grid. Grids in South Australia and Ireland already run for hours with very high shares of inverter-based power.

Step 6 of 15Practice · Put in order

Order the grid's responses to a sudden loss of a power plant, from fastest to slowest.

Drag the items, or use the arrow buttons, to put them in order.

  1. Governors on generators automatically increase output
  2. Inertia of spinning generators slows the frequency drop
  3. Automatic generation control restores frequency to target
  4. Operators bring extra plants online to rebuild reserves

Step 7 of 15Diagram

The defense layers after a plant trips

Each layer buys time for the next one. Tap to see the timescale.

The defense layers after a plant tripsProcess diagram: Plant trips → Inertia (0–10 s) → Governors (seconds) → AGC (minutes) → Operators (tens of minutes).Plant tripsInertia (0–10 s)Governors (seconds)AGC (minutes)Operators (tens ofminutes)

Tap a shape with to see more.

Plant trips

Supply suddenly drops below demand, and frequency starts to fall.

Inertia (0–10 s)

Spinning rotors release stored kinetic energy, slowing the fall.

Governors (seconds)

Generators sense the drop and open their throttles automatically.

AGC (minutes)

The control center's software raises output on selected plants to bring frequency back to 60 Hz.

Operators (tens of minutes)

Extra plants are started so reserves are ready for the next failure.

Step 8 of 15Learn

The daily load curve

Electricity demand, or load, follows a daily and seasonal rhythm. Plot it over 24 hours and you get a load curve. A typical pattern: demand is lowest around 3–5 a.m., rises as people wake and businesses open, stays high through the day, and peaks in the late afternoon or early evening when people come home, cook and switch on lights while offices are still running. In hot regions, air conditioning makes summer afternoons the highest peaks of the year; in cold regions with electric heating, winter evenings can peak highest.

Traditionally, grid planners divided generation into three roles:

  • Baseload: plants that run nearly all the time, covering the minimum demand that never goes away. Nuclear and many coal plants were built for this role because they have low fuel costs and do not like changing output quickly.
  • Intermediate (load-following): plants that ramp up and down with the daily cycle, often combined-cycle gas and hydro.
  • Peaking: plants that run only a few hundred hours a year during the highest demand, such as simple-cycle gas turbines. They are cheap to build but expensive to run.

The grid must be built to cover the peak, plus a safety margin called the reserve margin, often around 15%. That means a large share of power plant capacity sits idle most of the year, waiting for the hottest afternoon or coldest evening. Cutting peak demand is therefore extremely valuable, a theme you will meet again with storage and demand response.

Step 9 of 15Explore

A simple daily load curve

This model adds a morning bump and an evening peak to a base load. Move the sliders to change the size of each peak and see how much capacity the grid must have.

020406080 05101520
Approximate peak demand
32 GW
Capacity needed with 15% reserve margin
36.8 GW

Step 10 of 15Practice · Estimate

A region's highest expected demand is 40 GW. Planners want a 15% reserve margin. About how much generating capacity (in GW) must be available?

37.5 GW

Step 11 of 15Practice · Sort into groups

Sort each plant into the role it traditionally plays.

Tap an item, then tap its group (or drag it there).

Step 12 of 15Practice · Chart

How different plants stack up to follow the load curve

Baseload plants run all day, intermediate plants follow the daily swing, and peakers cover the highest hours.

Tap the hour when peaking plants are needed most.

Tap the bar that answers the question, then press Check.

How different plants stack up to follow the load curveStacked bar chart with 8 categories: 0:00: Baseload 20 GW, Intermediate 6 GW, Peaking 0 GW; 3:00: Baseload 20 GW, Intermediate 4 GW, Peaking 0 GW; 6:00: Baseload 20 GW, Intermediate 8 GW, Peaking 0 GW; 9:00: Baseload 20 GW, Intermediate 12 GW, Peaking 0 GW; 12:00: Baseload 20 GW, Intermediate 13 GW, Peaking 1 GW; 15:00: Baseload 20 GW, Intermediate 14 GW, Peaking 3 GW; 18:00: Baseload 20 GW, Intermediate 15 GW, Peaking 6 GW; 21:00: Baseload 20 GW, Intermediate 11 GW, Peaking 1 GW.0 GW10 GW20 GW30 GW40 GW50 GWOutput0:003:006:009:0012:0015:0018:0021:00Hour of day26 GW24 GW28 GW32 GW34 GW37 GW41 GW32 GW
Illustrative day for a traditional grid without large amounts of solar.
How different plants stack up to follow the load curve
Hour of dayBaseloadIntermediatePeaking
0:0020 GW6 GW0 GW
3:0020 GW4 GW0 GW
6:0020 GW8 GW0 GW
9:0020 GW12 GW0 GW
12:0020 GW13 GW1 GW
15:0020 GW14 GW3 GW
18:0020 GW15 GW6 GW
21:0020 GW11 GW1 GW

Step 13 of 15Practice · True or false

Because the grid must cover peak demand, a large share of generating capacity sits unused for most hours of the year.

Step 14 of 15Note

Step 15 of 15Practice · Choose one

Why does a grid operator deliberately cut power to some customers when frequency falls far below normal?