Capacity, Capacity Factor and Cost
Separate installed capacity from energy produced, calculate capacity factors, and understand what levelized cost of electricity does and does not tell you.
Welcome back!
Step 1 of 14Learn
A 100 MW plant does not make 100 MW
Headlines often say things like "the country installed 30 gigawatts of solar this year." That number is capacity: the maximum power the plants can produce under ideal conditions, also called nameplate capacity. It does not tell you how much energy they will actually generate, because no plant runs at full output every hour of the year.
The link between the two is the capacity factor:
Capacity factor = actual energy produced ÷ (capacity × hours in the period)
A year has 8,760 hours. A 100 MW plant running flat out all year would produce 100 × 8,760 = 876,000 MWh. If it actually produced 219,000 MWh, its capacity factor is 219,000 ÷ 876,000 = 25%.
Typical US capacity factors (they vary by site and year):
- Nuclear: above 90%. Plants run nearly nonstop, pausing every 18–24 months to refuel.
- Combined-cycle gas: around 55–60%.
- Coal: around 40–50% and falling, as cheaper gas and renewables push coal plants to run less.
- Wind: around 35%, higher offshore, often 40–50%.
- Hydro: around 35–40%, depending on rainfall.
- Utility-scale solar PV: around 20–25%, higher in deserts.
- Gas peakers: often below 10%, by design.
So 1 GW of solar produces roughly a quarter as much energy in a year as 1 GW of nuclear. Comparing technologies by capacity alone, without adjusting for capacity factor, is one of the most common errors in energy reporting.
Step 2 of 14Try the calculator
Capacity factor calculator
Enter a plant's capacity and its capacity factor to estimate yearly energy and how many average homes it could supply (assuming about 10,500 kWh per home per year).
- Energy per year
- 306,600 MWh
- Average output
- 35 MW
- Homes supplied (yearly average)
- 29,200 homes
Step 3 of 14Practice · Work it out
A 50 MW wind farm produces 153,300 MWh in a year. What is its capacity factor in percent?
Step 4 of 14Note
Step 5 of 14Learn
Why capacity factors differ
Low capacity factors happen for three very different reasons, and they mean different things.
- The resource is not always there. Solar panels produce nothing at night and less in winter and under clouds. Wind turbines need wind within a certain speed range. A solar farm's 25% capacity factor is not a flaw in the equipment; it reflects the sunlight available.
- The plant is not needed or is too expensive. A gas peaker could run all the time, but its fuel is expensive, so it is used only when prices are high. Many coal plants now run less because cheaper sources undercut them.
- Maintenance and outages. Every plant needs downtime for repairs and inspection. Nuclear plants are scheduled carefully to minimize this, which is why their capacity factor is so high.
Another key idea is dispatchability: whether operators can turn a plant up or down on command. Gas, hydro with reservoirs, coal and nuclear are dispatchable (though coal and nuclear change output slowly). Solar and wind are variable: they produce when nature allows and can be turned down (curtailed) but not up beyond what the weather provides. Batteries are dispatchable within the limit of their stored energy.
A grid needs both energy and firm capacity, power that will reliably be there during the peak. A solar farm in a summer-peaking region contributes some firm capacity at 3 p.m. but almost none at 8 p.m., when the evening peak may happen after sunset.
Step 6 of 14Practice · Match the pairs
Match each technology to its typical US capacity factor range.
Tap an answer, then tap the place where it belongs (or drag it there).
- Nuclear
- Combined-cycle gas
- Onshore wind
- Utility-scale solar PV
- Gas peaker
Step 7 of 14Practice · Chart
Average US capacity factors by technology
Which technology has a low capacity factor mainly by design, not because its resource is missing?
Tap the bar that answers the question, then press Check.
Step 8 of 14Learn
Levelized cost of electricity
How do you compare a solar farm, which is expensive to build but has free fuel, with a gas plant, which is cheaper to build but must buy fuel for decades? Analysts use the levelized cost of electricity (LCOE): the average cost per MWh over a plant's whole life.
LCOE ≈ (lifetime capital cost + lifetime operating and fuel costs) ÷ lifetime energy produced
Real calculations discount future costs and energy to present value, but the idea is simple: total cost divided by total output.
A simplified example. A plant costs $100 million to build, $2 million a year to run, and produces 200,000 MWh a year for 25 years. Total cost = $100 million + 25 × $2 million = $150 million. Total energy = 25 × 200,000 = 5,000,000 MWh. LCOE = $150,000,000 ÷ 5,000,000 = $30 per MWh, ignoring interest and discounting.
Over the 2010s, the LCOE of utility-scale solar fell by roughly 90% and onshore wind by about 70%, making them among the cheapest sources of new electricity in many countries.
But LCOE has limits. It treats every MWh as equal, whether produced at noon in spring, when power is plentiful, or at 7 p.m. in a heat wave, when it is precious. It ignores the cost of backup, storage and new transmission that variable sources may need, and it ignores pollution costs unless they are priced. A fair comparison looks at system costs: what it costs to run a reliable grid with a given mix.
Step 9 of 14Chart
What makes up the cost of a megawatt-hour
Two plants with similar LCOE can have opposite cost structures. Compare how much of each one's cost is paid up front.
| Item | Building (capital) | Operations and maintenance | Fuel |
|---|---|---|---|
| Solar PV | 80% | 20% | 0% |
| Onshore wind | 75% | 25% | 0% |
| Nuclear | 70% | 20% | 10% |
| Combined-cycle gas | 25% | 10% | 65% |
Step 10 of 14Try the calculator
Simplified LCOE (no discounting)
Total lifetime cost divided by total lifetime energy. Real analyses also discount future money; this simplified version shows the core trade-off between building cost and fuel cost.
- Lifetime cost
- 150 $ million
- Lifetime energy
- 5,000,000 MWh
- Levelized cost
- 30 $/MWh
Step 11 of 14Practice · Choose one
Why can two plants with the same LCOE have very different value to a grid?
Step 12 of 14Practice · True or false
If a country builds 10 GW of solar and 10 GW of nuclear, both will produce about the same amount of electricity per year.
Step 13 of 14Note
Step 14 of 14Practice · Work it out
How many GW of solar at a 23% capacity factor would produce the same yearly energy as 1 GW of nuclear at a 92% capacity factor?