How the price of electricity is set

In many regions, including much of the US, Europe and Australia, a wholesale electricity market decides which plants run each hour. Generators submit offers stating how much power they can supply and at what price. The grid operator stacks the offers from cheapest to most expensive, called the merit order, and accepts them in that order until supply meets demand.

Offers usually reflect each plant's marginal cost: the cost of producing one more MWh, mostly fuel. Wind, solar, hydro and nuclear have very low marginal costs, so they come first. Then come efficient gas plants, then older and less efficient plants, then peakers.

In most markets, every accepted generator is paid the price of the last (marginal) unit needed to meet demand. This is called uniform marginal pricing. If the last plant needed is a gas plant offering $60/MWh, every running plant receives $60/MWh, including wind farms with near-zero costs. That sounds generous to cheap plants, but it gives everyone a reason to offer their true costs, and the margin is what pays back their construction costs.

Consequences:

  • When demand is low or wind and solar are abundant, the marginal plant is cheap and prices fall, sometimes below zero.
  • During peaks, expensive peakers set the price, and prices can spike to hundreds or even thousands of dollars per MWh.
  • Gas prices often set electricity prices, because gas plants are so often the marginal unit. That is why European power prices soared when gas prices spiked in 2022.

Step 2 of 14Try the calculator

Merit order: who sets the price?

Three blocks of supply are offered at rising prices: renewables and nuclear, then gas combined-cycle, then peakers. Enter demand and see which block is marginal.

Market price (renewables/nuclear $5, gas $60, peakers $200)
60 $/MWh
Gas output needed
25 GW
Peaker output needed
0 GW

Step 3 of 14Practice · Work it out

A market has these offers: 20 GW of wind at $0/MWh, 10 GW of nuclear at $10, 15 GW of gas at $45 and 5 GW of peakers at $150. Demand is 40 GW. What is the market price in $/MWh under uniform marginal pricing?

Step 4 of 14Note

Step 5 of 14Practice · Chart

An illustrative merit order

Offers are stacked from cheapest to most expensive. Plants are switched on from left to right until demand is met.

Demand is high enough that some gas combined-cycle plants run, but no peakers. Which block sets the price paid to every running plant?

Tap the bar that answers the question, then press Check.

An illustrative merit orderBar chart with 5 categories: Wind and solar: $0; Nuclear: $10; Coal: $30; Gas combined-cycle: $45; Gas peakers: $150.$0$50$100$150Offer ($/MWh)Wind and solarNuclearCoalGascombined-cycleGas peakers$0$10$30$45$150
Illustrative offer prices.
An illustrative merit order
ItemOffer price
Wind and solar$0
Nuclear$10
Coal$30
Gas combined-cycle$45
Gas peakers$150

Step 6 of 14Learn

Who runs the grid and who sells power

Electricity systems are organized in different ways:

  • Vertically integrated utilities own power plants, transmission and distribution in their territory and sell directly to customers. A state public utility commission regulates their prices, usually letting them recover costs plus a set rate of return. Much of the southeastern and western US works this way.
  • Restructured markets split generation from the wires. Independent generators compete in wholesale markets run by independent system operators (ISOs) or regional transmission organizations (RTOs), such as PJM in the mid-Atlantic, ERCOT in Texas and CAISO in California. Local distribution companies still own the wires as regulated monopolies, because building duplicate wires would make no sense. In some states customers can choose their retail electricity supplier.

Wires are a natural monopoly: one network serving everyone is far cheaper than competing networks. Generation can be competitive.

Energy-only markets pay for MWh produced. Some regions add capacity markets, which pay plants to be available during future peaks whether or not they run, to ensure enough capacity is built. Texas relies on an energy-only market with very high price caps instead, betting that scarcity prices will attract investment.

Ancillary services are additional products the operator buys to keep the grid stable: frequency regulation, spinning and non-spinning reserves, voltage support and black start capability, the ability of a plant to start up without power from the grid after a total blackout.

Step 7 of 14Practice · Match the pairs

Match each term to its meaning.

Tap an answer, then tap the place where it belongs (or drag it there).

  1. Merit order
  2. Marginal unit
  3. Capacity market
  4. Black start
  5. Natural monopoly

Step 8 of 14Learn

Why blackouts happen

Large blackouts usually come from a chain of failures rather than one event.

August 14, 2003, Northeast US and Ontario. Overloaded transmission lines in Ohio sagged into trees that had not been trimmed. A software bug disabled the alarm system at a control room, so operators did not see the problem developing. As each line tripped, power shifted to others, which overloaded and tripped in turn. Within minutes, a cascade cut power to about 50 million people. Reliability standards became mandatory in the US afterward.

February 2021, Texas. Winter Storm Uri brought extreme cold across a grid whose gas wells, pipelines and power plants were largely not winterized. Gas supply froze, many gas, coal and nuclear units failed, and wind turbines without cold-weather packages iced up. Demand for heating soared at the same moment. Operators cut power to millions of customers for days to avoid total collapse, and hundreds of people died. Gas-fired generation accounted for the largest share of the lost output.

Grids are planned with the N−1 criterion: the system must keep running normally if any single major component, such as the largest generator or a key transmission line, fails unexpectedly. Some critical areas plan for N−2.

Common threats to reliability include extreme heat and cold, hurricanes, wildfires (and wildfires started by power lines), cyberattacks, and correlated failures where one cause, such as freezing weather or a fuel shortage, takes out many plants at once.

Step 9 of 14Practice · Spot the mistake

A news summary of the 2003 blackout contains errors. Tap the two incorrect statements.

Step 10 of 14Timeline

Major blackouts and what they taught

  1. 1965
    Northeast US and Ontario

    A misset relay tripped a line; 30 million people lost power. Led to the creation of regional reliability councils.

  2. 1977
    New York City

    Lightning strikes and slow operator response; looting followed. Strengthened operating rules.

  3. 2003
    Northeast US and Ontario

    Untrimmed trees and a failed alarm system; about 50 million affected. Reliability standards became mandatory.

  4. 2012
    Northern India

    Overdrawn grids collapsed over two days, affecting over 600 million people, the largest blackout by population.

  5. 2021
    Texas (ERCOT)

    Extreme cold froze gas supply and power plants; millions lost power for days.

  6. 2025
    Spain and Portugal

    On April 28 the Iberian grid collapsed within seconds, cutting power to tens of millions for most of a day.

Step 11 of 14Practice · True or false

Under uniform marginal pricing, a wind farm with near-zero fuel costs receives the same price per MWh as the gas plant that sets the market price in that hour.

Step 12 of 14Practice · Choose one

Why do grid planners apply the N−1 criterion?

Step 13 of 14Tap to reveal

What is inside a retail electricity bill

  1. Energy or generation charge

    The cost of the electricity itself, set by wholesale markets or the utility's own power plants. It is often only about half of the total bill.

  2. Transmission charge

    Pays for the high-voltage network that moves power from plants to your region.

  3. Distribution charge

    Pays for local poles, wires, transformers, meters and storm repairs. Often the second-largest part of the bill.

  4. Fixed customer charge

    A flat monthly fee that covers billing and the basic connection, charged even if you use no electricity.

  5. Riders, programs and taxes

    Funding for efficiency programs, low-income assistance, fuel cost adjustments and local taxes.

Step 14 of 14Practice · Choose one

Wholesale electricity prices fall by half for a month, but a household's retail bill drops only about 25%. What is the most likely explanation?